Vector control

6.1 Technology application (application) (p0500)

6.1
Technology application (application) (p0500)
Function description
Using parameter p0500, you can influence the calculation of open-loop control and closed-loop
control parameters. The default setting helps you find suitable values for standard applications.
You can make preassignments for the following technological applications:
Value p0500 Application
An overview of the influenced parameters and the set values is provided in the "SINAMICS
S120/S150 List Manual".
Instantiating the calculation of the parameters
You call the calculation of the parameters, which influence the technological application, as
follows:
● When exiting quick commissioning with p3900 > 0
● When automatically calculating the motor/closed-loop control parameters with
p0340 = 1, 3, 5 (for p0500 = 6: p0340 = 1, 3, 4)
● When calculating the technology-dependent parameters with p0578 = 1
208
0
Standard drive (vector)
1
Pumps and fans
2
Encoderless control down to f = 0 (passive loads)
4
Dynamic response in the field weakening range
5
Starting with high breakaway torque
6
High load moment of inertia (e.g. centrifuges)
Function Manual, 06/2019, 6SL3097-5AB00-0BP2