Removing An Mx10008 Fan Tray - Juniper MX10008 Hardware Manual

Universal routing platform
Table of Contents

Advertisement

Removing an MX10008 Fan Tray Controller | 186
Installing an MX10008 Fan Tray Controller | 188
An MX10008 router has two independent, field-replaceable fan trays. Fan trays must be replaced within
the duration mentioned in
Table 56: Replacement Duration for the Fan Tray
Chassis Ambient Temperature
27°C
35°C
40°C
NOTE:
When replacing the fans or SFBs at 40°C chassis ambient temperature, ensure that the
fans run at 100% fan speed for at least 10 minutes before replacing the fans or SFBs.
Use the test chassis fan tray 0 speed minutesfull-speed and test chassis fan tray 1 speed full-speed
commands to set the chassis fans to 100% speed.
To install or remove the fan trays and fan tray controller, see the following sections:

Removing an MX10008 Fan Tray

An MX10008 has two independent, field-replaceable fan trays. Each fan tray is a hot-removable and
hot-insertable field-replaceable unit (FRU); you can remove and replace the fan tray while the router is
running without turning off power to the router or disrupting routing functions. There are two models of
the fan tray, JNP10008-FAN and JNP10008-FAN2.
CAUTION:
Do not remove the fan tray unless you have a replacement fan tray available.
Each fan tray is installed vertically on the rear, or FRU-side, of the chassis.
Table 56 on page
179.
Duration
5 minutes
3 minutes
2 minutes
179