Chapter 5 Trial Run and Tuning Procedure|ASDA-A2 Series

5.6.7 Relationship between Tuning Modes and Parameters

Tuning Mode
Manual Mode
Auto Mode
[Continuous
Adjustment]
Semi-Auto Mode
[Non-continuous
Adjustment]
When switching mode #1 to #0, the setting value of P2-00, P2-02, P2-04, P2-06, P2-25, P2-26 and P2-
49 will change to the value that measured in #1 auto-tuning mode.
When switching mode #2 to #0, the setting value of P2-00, P2-02, P2-04, P2-06, P2-25, P2-26 and P2-
49 will change to the value that measured in #2 semi-auto tuning mode.
5-22
AutoSet
P2-32
Parameter
0(Default
None
setting)
P1-37
P2-00
P2-02
P2-04
1
P2-06
P2-25
P2-26
P2-49
P1-37
P2-00
P2-02
P2-04
2
P2-06
P2-25
P2-26
P2-49
User-defined Parameter
P1-37 (Ratio of Load Inertia to Servo Motor
Inertia [J_load / J_motor])
P2-00 (Proportional Position Loop Gain)
P2-04 (Proportional Speed Loop Gain)
P2-06 (Speed Integral Compensation)
P2-25 (Low-pass Filter Time Constant of
Resonance Suppression)
P2-26 (External Anti-Interference Gain)
P2-31 (Auto Stiffness and Frequency
response Level)
P2-31 (Auto Stiffness and Frequency
response Level)
Gain Value
Fixed
Continuous
Adjusting
(every 30
minutes)
Non-
continuous
Adjusting
(stop after a
period of
time)
Revision April, 2010