Chapter 5 Trial Run and Tuning Procedure|ASDA-A2 Series
5.6.5 Limit of Load Inertia Estimation
The accel. / decel. time for reaching 2000r/min must be below 1 second. The rotation speed must be
above 200 r/min. The load inertia must be 100 multiple or less of motor inertia. The change of external
force and the inertia ratio can not be too much. In Auto Mode (P2-32 is set to 1), the measured load
inertia value will be saved automatically and memorized in P1-37 every 30 minutes. In Semi-Auto Mode,
it will stop estimating the load inertia after a period of continuous adjustment time when the system
inertia becomes stable. The measured load inertia value will be saved automatically and memorized in
P1-37 when load inertia estimation is stopped.
5-19
Revision April, 2010