Chapter 7 Motion Control Function|ASDA-A2 Series

7.2.1 Monitor Variables

Please refer to the following table for the explanation of monitor variables:
Item
Variable
Each monitor variable has one corresponding code. The parameter P0-02 is used to
Code
set this code and monitor the monitor variable.
Format
Each monitor variable is saved in 32-bit (long integer) in the servo drive.
There are two types of monitor variables, basic variable and extension variable:
1.
Type
There are two kinds of methods for monitoring the monitor variables, one is through
LED display of the digital keypad and the other is via mapping parameters:
1.
Monitor
Method
2.
1.
2.
Display
Press SHIFT key to switch high/low byte display;
Press SET key to switch decimal/hexadecimal display.
1. The parameters which support mapping function includes: P0-09 ~ P0-13. (Please
2. Using mapping parameters and read & write monitor variables through
3. The setting values of P0-09 ~ P0-13 (Status Monitor 1 ~ 5) are the content of basic
Mapping
Function
Attribute of monitor variables:
Attribute
B
Basic variable. The monitor variables which can be scrolled through by pressing
UP/DOWN keys.
Dn
Decimal place display.
D1
Dec
Decimal display only. When pressing SET key on the keypad, the system can not
switch to hexadecimal display.
Hex
Hexadecimal display only. When pressing SET key on the keypad, the system can not
switch to decimal display.
7-2
Basic variable: Enter into monitor mode by pressing MODE key on the digital
keypad. In monitor mode, press UP/DOWN arrow keys to find the available
monitor variables (P0-02=0~26).
Extension variable: Other variables are called extension variables except basic
variables (P0-02=27~127).
LED display of digital keypad: Monitor the monitor variables through the LED
display of the digital keypad directly.
Mapping parameters: The settings of monitor variables will be reflected on the
setting value of the parameters. The users can know the settings of monitor
variables through the corresponding parameters.
Press MODE key to switch to monitor mode and then press UP/DOWN arrow
keys to select the desired monitor variables.
Set P0-02 directly and then display the settings of the desired monitor variables.
"
refer to section 8.3
Detailed Parameter Listings" of Chapter 8.
communication.
variables (17h,18h,19h,1Ah). When the users want to monitor P0-09, P0-17 must
be set first to read the status value (see P0-02). When reading the drive status
through Modbus communication, the system will read the monitor status which
specified by P0-17. When reading the drive status through the keypad, if P0-02 is
set to 23, VAR-1 will quickly show for about two seconds and then the value of P0-
09 will display on the display.
indicates one decimal place,
Explanation
Explanation
D2
indicates two decimal place.
Revision April, 2010