Testing Manual Call Points - Siemens AlgoPilot B3Q661 Operating Instructions Manual

Table of Contents

Advertisement

Testing MANUAL CALL POINTS

The system must be switched to test mode before testing can begin.
Switching over
F
to test mode
Also refer to following chapter:
· "TEST CONDITION per SECTION" on page 42
· "TEST CONDITION per LINE" on page 44
· "TEST CONDITION per ZONE" on page 46
This procedure describes the test principle for manual call points of AlgoRex type DM1101,
Testing DM11x1
DM1131, DM1151 (type KAC) and Sinteso
/ FDM221 type
manual call
Perform the following steps to test these types of manual call point:
points
Step
NOTE:
Once testing is complete, the 'Test condition' operating mode must be ended.
F
Also refer to following chapter:
· "TEST CONDITION per SECTION" on page 42
· "TEST CONDITION per LINE" on page 44
· "TEST CONDITION per ZONE" on page 46
48
Building Technologies
Fire Safety
Action
Set corresponding manual call
1
point zones to 'Test condition' op-
erating mode
Insert test key in opening: à 'Test
2
alarm' is simulated
Wait until response indicator on
3
manual call point flashes
Remove test key
4
Operating instructions Œ•Ž
TM
type FDM221.
Result / Comment
The function test is complete.
Continue with the next manual call
point
Test key
A6V10225450_b_en_--