Switching INDIVIDUAL ZONE OFF/ON,
The method used to switch the zone OFF have no impact on the steps required to switch the
Switching ON an
zone ON.
individual zone
Perform the following steps to switch a zone ON:
Step
Building Technologies
Fire Safety
Action
Press button
1
<Isolation>
Use the scroll keys to select the
2
zone to be switched ON
Press softkey
3
<Functions for
sel. message..>
Press softkey
4
<ON/OFF functions>
Press softkey
5
<Zone -> ON>
Operating instructions Œ•Ž
continued
Result / Comment
Isolation messages appear on the
display
The zone selected is displayed in-
versely
The sub-menu is displayed
Implementation messages
'Implementing ...'
'Implemented'
- and -
29
A6V10225450_b_en_--
2017.09.07