Localizing OPEN LINE

This function is a great help in establishing the precise location of an open line. Once this com-
What should be
mand has been executed, the detector line is only controlled from one side. The terminal lists all
done?
invisible devices from the corresponding direction. Once both commands have been used, the
service engineer can search within a small area, locate and remedy the open line.
· This function is not available for Sinteso
i
· Establish and remedy the fault display for an open line via AlgoWorks. (For application and
rectification –> See AlgoWorks Online Help)
This function is only available with interactive detector lines.
i
It is only useful on loop lines.
Separates the loop line path which faces backwards.
Stub line opera-
tion
forwards
Separates the loop line path which faces forwards.
Stub line opera-
tion
backwards
This command ends stub line operation.
Switching back
Stub line operation is also ended when the station is restarted.
to normal opera-
tion
If you still don't have operating access when starting operation work, the release procedure is
Operating ac-
automatically called up.
cess