REPLACING AlgoRex DEVICE

The process of replacing AlgoRex interactive manual call points and DC modules is a simple
Simple replace-
one. If the device is found to be defective, the corresponding element can be set using the
ment process
'Replace device -> On operating mode' to the 'Replace device' operating mode command.
for AlgoRex
The operating personnel can then replace the defective device.
manual call
points and DC
modules
If you still don't have operating access when starting operation work, the release procedure is
Operating ac-
automatically called up.
cess
The command is available at element level. A message to this effective is displayed on the ter-
minal. Only one element can be replaced per replacement session. The 'Replace device -> Off
Replace device -
operating mode' or restarting the station ends this operating mode.
> On operating
mode
Perform the following steps to set a defective manual call point to 'Replace' operating mode:
Step
This command switches off the supply to the line to which the element selected is connected.
66
Building Technologies
Fire Safety
Action
Press button <Faults>
1
Select defective manual call point
2
Press softkey
3
<Functions for sel. message..>
Press softkey
4
<More functions..>
Press softkey
5
<Device replace mode -> ON>
Operating instructions Œ•Ž
Result / Comment
Use the scroll keys on the display
Implementation messages
'Implementing ...'
'Implemented'
A6V10225450_b_en_--