TEST CONDITION per ZONE

F
NOTE
For general information about the 'Test condition' operating mode, see chapter "TEST
CONDITION per SECTION" on page 42.
If you still don't have operating access when starting operation work, the release procedure is
Operating ac-
automatically called up.
cess
Perform the following steps to set one individual detector zone to 'Test condition' operating
Switching on
mode:
'Test condition'
operating mode
Step
Perform the following steps to end 'Test condition' operating mode for one individual detector
Ending 'Test
zone:
condition'
operating mode
Step
46
Building Technologies
Fire Safety
Action
Navigate to the ZONE you want us-
1
ing:
<Operate..>
<Browse..>
<Browse FIRE DETECTION..>
<Browse EXTINGUISHING..>
<Select SECTION¯>
<Select ZONE¯>
Press softkey
2
<TEST/RENOVATION/
INST.TEST funct..>
Press softkey
3
<Zone -> TEST>
Action
Press <Isolation> button
1
Select detector zone, which is to be
2
reset to 'Normal operation'
Press softkey
3
<Functions for sel. message..>
Press softkey
4
<TEST/RENOVATION/
INST.TEST funct..>
Press softkey
5
<Zone -> TEST OFF>
t
t
- or -
t
t
Operating instructions Œ•Ž
Result / Comment
The zone functions are displayed
Implementation messages
'Implementing ...'
'Implemented'
Result / Comment
Use the scroll keys on the display
Implementation messages
'Implementing ...'
'Implemented'
A6V10225450_b_en_--
- and -
- and -
2017.09.07