TEST CONDITION per SECTION,
Perform the following steps to set all detector zones within a SECTION to 'Test condition' oper-
Switching on
ating mode:
'Test condition'
operating mode
Step
Perform the following steps to end 'Test condition' operating mode for all detector zones within a
Ending 'Test
SECTION:
condition'
operating mode
Step
Building Technologies
Fire Safety
Action
Navigate to the SECTION you want
1
using:
<Operate..>
<Browse..>
<Browse FIRE DETECTION..>
<Browse EXTINGUISHING..>
<Select SECTION¯>
Press softkey
2
<DETECTOR zone functions..>
Press softkey
3
<All DETECTOR zones -> TEST>
Action
Press button <Isolation>
1
Select one of the detector zones to be
2
reset to 'Normal operation'
Press softkey
3
<Functions for sel. message..>
Press softkey
4
<Select SECTION->
Press softkey
5
<DETECTOR zone functions..>
Press softkey
6
<All DETECTOR zones
-> TEST OFF>
continued
t
t
- or -
t
Operating instructions Œ•Ž
Result / Comment
The section functions are dis-
played
Implementation messages
'Implementing ...'
'Implemented'
Result / Comment
Use the scroll keys on the display
Implementation messages
'Implementing ...'
'Implemented'
A6V10225450_b_en_--
- and -
- and -
43
2017.09.07