Detector parameter sets,
Parameter sets for interactive HEAT detectors.
Interactive
HEAT detectors
Parameter sets available
APS100T
APS103T
APS105T
APS107T
Parameter sets for interactive SMOKE/HEAT detector DOTE1152.
Interactive
SMOKE/HEAT
With DOTE1152 all the parameter sets available for detectors of the DOT115x series can be
detector
used; the DOTE1152 does then behave in exactly the same way as a DOT115x, i.e. no carbon
DOTE1152
monoxide evaluation! The carbon monoxide evaluation is only activated by selecting one of the
special parameter sets for DOTE1152. These parameter sets are labeled as "SE".
The detector DOTE1152 is a very powerful smoke detector according to EN54-7.
It is not a carbon monoxide warning device, and it will never indicate a carbon monoxide warn-
ing to the control panel.
Parameter sets
and detector types
APS207SE
APS213SE
APS216SE
parameter
sets for
DOT115x
Building Technologies
Fire Safety
continued
and detector types
DT1152
DT1151-Ex
APS = Algo parameter set (reference number shown on display)
T
= Thermal
1) Response characteristics: Temperature rise (gradient) or maximum
temperature at which an alarm is activated
available
Smoke sensitivity index
1 Õ 2 without thermal influ-
ence
2 Õ 5 with max. thermal in-
fluence
1 Õ 2 without thermal influ-
ence
2 Õ 5 with max. thermal in-
fluence
2 Õ 4 without thermal influ-
DOTE1152
ence
5 Õ 8 with max. thermal in-
fluence
All
APS = Algo parameter set (reference number shown on display)
SE
= Smoke/heat/carbon monoxide
Response characteristics 1)
Rate of rise
maximum temperature > 60oC
and
Maximum temperature > 60oC
Rate of rise
maximum temperature > 80oC
and
Maximum temperature > 80oC
'Manned'
operating
mode
110 Õ 60
sec
110 Õ 60
sec
60 sec
Identical to DOT115x
Basic system information &
Response time
'Unmanned'
'Renovation'
operating
operating
mode
mode
Does not
110 Õ 40
respond to
smoke (heat
sec
only)
Does not
110 Õ 40
respond to
sec
smoke (heat
only)
Does not
respond to
40 Õ 30 sec
smoke (heat
only)
A6V10225450_b_en_--