INSTALLATION TEST,
Perform the following steps to reset one individual detector zone to 'Normal operation':
Resetting
one individual
detector zone to
'Normal
operation'
Step
Setting all de-
Perform the following steps to set all detector zones to 'Installation test' operating mode:
tector zones
within one
SECTION to
'Installation test'
operating mode
Step
Building Technologies
Fire Safety
continued
Action
Press button <Information>
1
Select detector zone, which is to be
2
reset to 'Normal operation'
Press softkey
3
<Functions for sel. message..>
Press softkey
4
<TEST/RENOVATION/INST.TEST
Press softkey
5
<Zone -> INST. TEST OFF>
Action
Navigate to the ZONE you want us-
1
ing:
<Operate..>
<Browse..>
<Browse FIRE DETECTION..>
<Browse EXTINGUISHING..>
<Select SECTION¯>
Press softkey
2
<DETECTOR zone functions..>
Press softkey
3
<All DETECTOR zones
-> INST. TEST>
funct..>
t
t
- or -
t
Operating instructions Œ•Ž
Result / Comment
Use the scroll keys on the display
F
see note below
Implementation messages
'Implementing ...'
'Implemented'
Result / Comment
The zone functions are displayed
Implementation messages
'Implementing ...'
'Implemented'
A6V10225450_b_en_--
- and -
- and -
51