Alarm / CAC: Cerberus alarm concept,
The operating mode and detector type determine whether CAC is used or not:
Dependencies
Danger message
Manual call point
activated
Automatic fire de-
tector
activated
Building Technologies
Fire Safety
continued
'Manned'
operating mode
The remote alarm transmission is activated
immediately.
The remote alarm transmission is delayed
during a brief V1 time to give the person re-
sponsible time to decide what measures to
take.
This person will generally acknowledge the
alarm which triggers the V2 time. The fire lo-
cation can be found during this time.
At the fire location, you must decide whether it
is a real fire and whether the fire brigade has
to intervene. If this is the case, the nearest
manual call point should be activated.
In the case of a minor incident, the person
takes the necessary measures himself/herself
and resets the alarm.
If the person responsible does not manage to
acknowledge the alarm within V1 and/or to
reset it within V2, the remote alarm transmis-
sion is activated automatically.
Basic system information &
'Unmanned'
operating mode
The remote alarm
transmission is acti-
vated immediately.
The remote alarm
transmission is acti-
vated immediately.
A6V10225450_b_en_--
2017.09.07
115