Siemens AlgoPilot B3Q661 Operating Instructions Manual page 122

Table of Contents

Advertisement

Detector parameter sets,
Parameter sets for interactive SMOKE detectors.
Interactive
SMOKE detec-
tors
Parameter sets available
and detector types
APS005S
DO1151/52
APS006S
APS007S
DOT1151/52
APS009S
DOT1151-Ex
APS015S
APS019S
APS081S
DOT1151/52
DOT1151-Ex
APS082S
for China only
APS085S
APS070SH
DO1153
APS071SH
APS072SH
nur Luftproben-
Rauchmelde-
APS073SH
systeme
APS = Algo parameter set (reference number shown on display)
S
SH
ASD = Active air sampling smoke detection system
122
Building Technologies
Fire Safety
continued
Smoke sensitivity index
DO:
2
DOT:
1
without thermal influence
2
with max. thermal influence
DO:
2
DOT:
1
without thermal influence
2.5
with max. thermal influence
DO:
4
DOT:
2
without thermal influence
5
with max. thermal influence
DO:
4
DOT:
2
without thermal influence
4
with max. thermal influence
1
ence
2
with max. thermal influence
2
ence
4
with max. thermal influence
4
ence
8
with max. thermal influence
Similar to APS005S, but with
adapted thermal detection part
in order to also satisfy the Chi-
nese requirements for heat de-
tectors
1.4
ence
4.3
with max. thermal influence
20Õ30 increasing sensitivity
during a smoldering fire
which is developing very slowly
20
12
6
= Smoke
= Smoke, high sensitivity
without thermal influ-
without thermal influ-
without thermal influ-
without thermal influ-
Basic system information &
Response time
'Unmanned'
'Manned' op-
operating
erating mode
mode
90 sec
90 sec
110 sec
110 sec
60 sec
30 sec
60 sec
40 sec
60 sec
30 sec
60 sec
40 sec
90 sec
90 sec
110 sec
110 sec
85 sec
85 sec
85 sec
85 sec
60 sec
30 sec
75 sec
45 sec
45 sec
45 sec
45 sec
45 sec
30 sec
30 sec
30 sec
30 sec
A6V10225450_b_en_--