Quick Start Wizard Via Simatic Pdm - Siemens SITRANS LR560 Operating Instructions Manual

Radar transmitters ma/hart
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

7.1.1.5

Quick Start Wizard via SIMATIC PDM

The graphic Quick Start Wizard provides an easy step-by-step procedure that configures the
device for a simple application.
Please consult the operating instructions or online help for details on using SIMATIC PDM.
1. If you have not already done so, check that you have the most up-to-date Electronic Device
Description (EDD) for your device. [See Configuring a new device (Page 60).]
2. Launch SIMATIC Manager and create a new project. Application Guides for setting up HART
and PROFIBUS PA devices with SIMATIC PDM can be downloaded from the product page of
our website:
LR560 (www.siemens.com/LR560)
Quick start
Note
• A reset to Factory Defaults should be performed before running the Quick Start Wizard if
device has been used in a previous application. See Master Reset via SIMATIC PDM
(Page 74).
• The Quick Start wizard settings are inter-related and changes apply only after you click
on FINISH AND DOWNLOAD at the end of the last step to save settings offline and
transfer them to the device.
• Do not use the Quick Start Wizard to modify individual parameters: for quick access to
echo profile parameters, see Echo Profile via SIMATIC PDM (Page 68) or see Parameter
Reference (Page 105) for a complete list. (Perform customization only after the Quick
Start has been completed.)
• Click on BACK to return and revise settings or CANCEL to exit the Quick Start.
• For a vessel with obstructions see Auto False Echo Suppression via SIMATIC PDM
(Page 69).
Launch SIMATIC PDM, open the menu Device – Wizard - Quick Start, and follow steps 1 to 4.
SITRANS LR560 (mA/HART)
Operating Instructions, 06/2017, A5E34647946-AD
Operating
7.1 Remote operation
61

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans l series

Table of Contents