Unit (2.2.5.); Calibration (2.3.); Low Calibration Point (2.3.1.); High Calibration Point (2.3.2.) - Siemens SITRANS LR560 Operating Instructions Manual

Radar transmitters ma/hart
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

8.2.2.5

UNIT (2.2.5.)

Factory setting:
Setting range:
Purpose:
Description:
8.2.3

CALIBRATION (2.3.)

8.2.3.1

LOW CALIBRATION POINT (2.3.1.)

Factory setting:
Setting range:
Purpose:
Description:
Related parameters:
The point from which level measurement is referenced.
1)
8.2.3.2

HIGH CALIBRATION POINT (2.3.2.)

Factory setting:
Setting range:
Purpose:
Description:
Related parameters:
The point from which level measurement is referenced.
1)
SITRANS LR560 (mA/HART)
Operating Instructions, 06/2017, A5E34647946-AD
m
m, cm, mm, ft, in, %
PV (Primary Value) and SV (Secondary Sensor measurement units). Used
in setting High/Low Calibration Point, and displayed on LCD and in PDM.
Changing units to % will update the mA setpoints.
40.000 m or 100.000 m
0.000 to 40.000 m or 0.000 to 100.000 m.
Distance from sensor reference point
defined in UNITS (2.2.1.) (Page 111) and displayed on the LCD and in
PDM.
Any change to Low Calibration Point will cause the mA setpoints to be
updated.
FAR RANGE (2.7.2.) (Page 121)
UNITS (2.2.1.) (Page 111)
0.000 m
0.000 to 40.000 m or 0.000 to 100.000 m.
Distance from sensor reference point
defined in UNITS (2.2.1.) (Page 111)
When setting the High Calibration Point value, note that echoes are ignored
within NEAR RANGE (2.7.1.) (Page 121).
Any change to High Calibration Point will cause the mA setpoints to be
updated.
UNITS (2.2.1.) (Page 111)
FAR RANGE (2.7.2.) (Page 121)
Parameter Reference
8.2 SETUP (2.)
to Low Calibration Point. Units are
1)
to High Calibration Point. Units are
1)
113