8.2.6.2
4 mA SETPOINT (2.6.2.)
Factory setting:
Setting range:
Purpose:
Description:
Related parameters:
8.2.6.3
20 mA SETPOINT (2.6.3.)
Factory setting:
Setting range:
Purpose:
Description:
Related parameters:
8.2.6.4
MIN. mA LIMIT (2.6.4.)
Factory setting:
Setting range:
Purpose:
SITRANS LR560 (mA/HART)
Operating Instructions, 06/2017, A5E34647946-AD
0.00 m
–999999 to +999999 (limits vary with current function and units)
Sets the process level corresponding to the 4 mA value. 4 mA always de-
faults to 0, and CURRENT OUTPUT FUNCTION (2.6.1.) (Page 117) de-
termines whether this is a Level, Space, or Distance measurement.
Enter the reading that is to correspond to a 4 mA output.
•
Units are defined in Units (2.2.1.) (Page 111) for Level, Space, or Dis-
•
tance.
UNITS (2.2.1.) (Page 111)
LOW CALIBRATION POINT (2.3.1.) (Page 113)
HIGH CALIBRATION POINT (2.3.2.) (Page 113)
40.00 m or 100.0 m (set to value corresponding to 100% as defined by
Current Output Function)
–999999 to +999999 (limits vary with current function and units)
Sets the process level corresponding to the 20 mA value. 20 mA always
defaults to 100%, and Current Output Function determines whether this is a
Level, Space, or Distance measurement, see CURRENT OUTPUT
FUNCTION (2.6.1.) (Page 117)
Enter the reading that is to correspond to a 20 mA output.
•
Units are defined in UNITS (2.2.1.) (Page 111) for Level, Space, or
•
Distance.
UNITS (2.2.1.) (Page 111)
LOW CALIBRATION POINT (2.3.1.) (Page 113)
HIGH CALIBRATION POINT (2.3.2.) (Page 113)
CURRENT OUTPUT FUNCTION (2.6.1.) (Page 117)
3.8 mA
3.56 to 22.6 mA
Prevents the mA output from dropping below this minimum level for a
measurement value. This does not restrict the Fail-safe or Manual settings.
Parameter Reference
8.2 SETUP (2.)
119