Siemens SITRANS LR560 Operating Instructions Manual page 74

Radar transmitters ma/hart
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

To set Service/Calibration schedules:
1. Open the menu Device – Maintenance, and click on the Service/Calibration Schedule tab.
2. Modify desired values and if desired, set reminders for either or both of Reminder 1 before
Lifetime (Required)/Reminder 2 before Lifetime (Demanded).
3. Click Write.
4. Click Read, to see the effects of your modification.
5. Click Service/Calibration Performed to reset the schedule.
Select analog output
Allows you to set the mA Output to report Level, Distance, or Space.
If a volume application is selected, mA Output is automatically set to Volume.
1. Open the menu Device – Select Analog Output.
2. Select Analog Output window displays the current setting: click OK.
3. Select a different setting and click OK.
4. Select Analog Output window displays the new setting: click OK.
Self test
Checks memory (RAM and Flash). If there are no errors, returns the message 'Self Test OK.' If
errors are found, returns the message 'Self Test Fails'.
Open the menu Device – Self Test, select Yes and click OK.
Loop test
Note
The simulated AO (Analog Output) value influences output to the control system.
Allows you to input a simulated value (4 mA, 20 mA, or a user-defined value) in order to test the
functioning of the mA connections during commissioning or maintenance of the device. The
range is 3.56 mA to 22.6 mA, see mA Output Value (2.6.6.).
To simulate a user-defined mA value:
1. Open the menu Device – Loop Test.
2. Select Other, enter the new value, and click on OK. The message 'Field Device fixed at [new
value]' appears. Click on OK. The Loop Test window remains open.
3. When you are ready to end simulation, select End and click on OK to return the device to the
actual output value.
SITRANS LR560 (mA/HART)
Operating Instructions, 06/2017, A5E34647946-AD
Operating
7.1 Remote operation
73

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans l series

Table of Contents