Units (1.4.)
Select the units for the Quick Start variables (high and low calibration point, and level,
distance, or space).
Options
High Calibration Point (CAL HIGH) (1.5.)
Distance from Sensor Reference to High Calibration Point: usually process full level.
Values
Low Calibration point (CAL LOW) (1.6.)
Distance from Sensor Reference to Low Calibration Point: usually process empty level.
Values
Rate (1.7.)
Sets the reaction speed of the device to measurement changes in the target range.
Options
Use a setting just faster than the maximum filling or emptying rate (whichever is greater).
Slower settings provide higher accuracy. Faster settings allow for more level fluctuation.
Apply Changes (APPLY?) (1.8.)
In order to save the Quick Start settings it is necessary to enable Apply Changes.
Options
Select YES. SITRANS LR460 is now ready to operate and returns to RUN mode.
6.2.8

Quick start wizard via SIMATIC PDM

The graphical Quick Start Wizard groups together all the settings you need to make for a
simple application into 4 steps.
To use HART or PROFIBUS PA, you will need a PC configuration tool: we recommend SIMATIC
PDM.
Please consult the operating instructions or online help for details on using SIMATIC PDM.
(Application Guides for setting up Siemens PROFIBUS PA and HART instruments with SIMATIC
PDM are available on our website: Process automation
(www.siemens.com/processautomation).
SITRANS LR460
Operating Instructions, 10/2021, A5E42035355-AB
MM, CM, M, IN, FT
Range
Range
SLOW
MED
FAST
YES, NO
0.0000 to 100.00 m
0.0000 to 100.00 m
0.1 m/minute
1.0 m/minute
10.0 m/minute
Commissioning
6.2 Quick start