8.5 COMMUNICATION (5.)

8.5
COMMUNICATION (5.)
8.5.1

DEVICE ADDRESS (5.1.)

Factory setting:
Setting range:
Purpose:
Description:
Range should be limited to 0 to 15 for a HART 5 master.
1)
Note
Process dependent on HART version
For HART 5 devices, this was a one step process. With HART 6 and above, this is a two-
step process.
Note
SIMATIC PDM
SIMATIC PDM only allows addresses 0-15.
8.5.2

REMOTE LOCKOUT (5.2.)

Factory setting:
Setting range:
Purpose:
146
0
0 to 63
1)
Sets the device address or poll ID on a HART network. For point-to-point
configurations, the standard address is 0. For multidrop configurations, use
a non-zero HART address.
To place the LR560 into HART multidrop:
Set the mA Output Mode (2.6.6.) to Fixed.
Set the Device Address to a non-zero value.
To set Device Address via SIMATIC PDM:
Open the project in Process Device Network View then right-click on the
device.
Go to Object Properties > Connection to access the field Short Address.
OFF
OFF, ON
Enables/disables the read/write access to parameters via remote commu-
nications. If locked via the handheld programmer, it can be unlocked only
via the handheld programmer. If locked via AMS, it can be reset via AMS.