Parameter Reference
8.4 SERVICE (4.)
8.3.13.9
ACKNOWLEDGE (3.7.9.)
Purpose:
Description:
8.4
SERVICE (4.)
8.4.1
DEMO MODE (4.1.)
Factory setting:
Setting range:
Purpose:
8.4.2
MASTER RESET (4.2.)
Note
• Following a reset to Factory Defaults, the LCD displays the Quick Start wizard.
• Following a reset to Factory Defaults, complete reprogramming is required.
Factory setting:
Setting range:
138
Acknowledges the current maintenance reminder.
To acknowledge a reminder via SIMATIC PDM:
Open the menu Diagnostics > Device Diagnostics and click on the tab
•
Maintenance.
In the Calibration Schedule section, click on Acknowledge Warnings.
•
To acknowledge a reminder via the local control buttons or hand-held program-
mer:
Press RIGHT arrow twice to open parameter view and activate Edit Mode.
•
Press RIGHT arrow to acknowledge the reminder.
•
OFF
ON or OFF
Used to set up for demonstrations: reduces the time between measure-
ments and the accuracy for demonstration purposes.
Factory Defaults
Factory Defaults, Warm Start
SITRANS LR560 (mA/HART)