Remind. 1 (Required) (3.6.3.); Remind. 2 (Demanded) (3.6.4.); Reminder Activation (3.6.5.); Lifetime Expected (3.6.6.) - Siemens SITRANS LR560 Operating Instructions Manual

Radar transmitters ma/hart
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

Parameter Reference
8.3 DIAGNOSTICS (3.)
8.3.12.3

REMIND. 1 (REQUIRED) (3.6.3.)

Factory setting:
Setting range:
Purpose:
Description:
8.3.12.4

REMIND. 2 (DEMANDED) (3.6.4.)

Factory setting:
Setting range:
Purpose:
Description:
8.3.12.5

REMINDER ACTIVATION (3.6.5.)

Factory setting:
Setting range:
Purpose:
Description:
8.3.12.6

LIFETIME EXPECTED (3.6.6.)

Note
The device always operates in years. Changing the units affects only the parameter view of
the Remaining Device Lifetime parameters in SIMATIC PDM.
Factory setting:
Setting range:
Purpose:
Description:
134
0.164 years
0 to 20 years
If REMAINING LIFETIME (3.6.2.) (Page 133) is equal to or less than this
value, the device generates a Maintenance Required reminder.
1) Modify values as required.
2) Set REMINDER ACTIVATION (3.6.5.) (Page 134).
0.019 years
0 to 20 years
If REMAINING LIFETIME (3.6.2.) (Page 133) is equal to or less than this
value, the device generates a Maintenance Demanded reminder.
1) Modify values as required.
2) Set REMINDER ACTIVATION (3.6.5.) (Page 134).
OFF
Reminder 1 (Maintenance Required), Reminder 2 (Maintenance Demand-
ed), Reminders 1 and 2, OFF
Allows you to enable a maintenance reminder.
To modify this parameter via SIMATIC PDM:
Go to menu Device – Maintenance.
10.00 years
0 to 20 years
Allows you to override the factory default.
Units: hours, days, years, are selectable only via SIMATIC PDM.
SITRANS LR560 (mA/HART)
Operating Instructions, 06/2017, A5E34647946-AD

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans l series

Table of Contents