Low calibration point
Factory setting:
Setting range:
Purpose:
High calibration point
Factory setting:
Setting range:
Purpose:
SITRANS LR560 (mA/HART)
Operating Instructions, 06/2017, A5E34647946-AD
Level
sensor reference point
20 mA, 100%
low calibration point
40.000 m or 100.000 m
0.000 to 40.000 m or 0.000 to 100.000 m
Distance from Sensor Reference to Low Calibration Point: usually process
empty level. See Operating (Page 59) for an illustration.
Parameter view
0.000 m
0.000 to 40.000 m or 0.000 to 100.000 m
Distance from Sensor Reference Point to High Calibration Point: usually
process full level. See Operating (Page 59) for an illustration.
Parameter view
6.5 Commissioning via handheld programmer
Space
high calibration point
4 mA, 0%
Commissioning
Distance
Edit mode
Edit mode