Siemens SITRANS LR560 Operating Instructions Manual page 108

Radar transmitters ma/hart
Hide thumbs Also See for SITRANS LR560:
Table of Contents

Advertisement

Make sure the material level is below all known obstructions.
1. Navigate to Level Meter >DIAGNOSTICS (3.) (Page 129)>
ECHO PROFILE (3.2.) (Page 130).
2. Press RIGHT
3. Determine a range that includes the false echo but not the
true echo: in the example, 3.3 m.
4. Open the AFES wizard.
5. Press DOWN
RIGHT
pression Range.
6. Enter the new range value and press RIGHT
it. Press DOWN
pears, followed by the message Wizard Complete.
7. Press DOWN
and return to Program menu.
8. Press LEFT
SITRANS LR560 (mA/HART)
Operating Instructions, 06/2017, A5E34647946-AD
to request a profile.
to continue and then
to edit Auto False Echo Sup-
to initiate learn. A transition screen ap-
(Finish) to save AFES parameter changes
twice to return to Measurement mode.
Parameter Reference
8.1 WIZARDS (1.)
① false echo ② AFES
to transfer
① false echo ② true echo
range
③ true echo
107