6.6
Application example
The application is a vessel that takes an average 3 hours (180 minutes) to fill and 3 weeks to
empty.
Fill rate
Therefore SLOW response rate (0.1 m/minute) can be selected.
①
②
③
④
⑤
⑥
Quick Start Parameter
Vessel
Response Rate
Units
Operation
Low Calibration Point
High Calibration Point
Wizard Complete
SITRANS LR560 (mA/HART)
Operating Instructions, 06/2017, A5E34647946-AD
= 0.08 m/minute [(Low Cal Pt. minus High Cal Pt.) / fastest of fill or empty time]
= (15.5 m – 1 m) / 180 min.
= 14.5 m /180 min. = 0.08 m/min.
sensor reference point
high calibration point
1.0 m
15.5 m
level
low calibration point
Setting
Description
STEEL
Selects vessel construction material.
SLOW
Resets fill rate and empty rate to 0.1 m/minute.
m
Sensor measurement units.
LEVEL
Material level referenced from low calibration point
15.5
Process empty level.
1.0
Process full level.
FINISH
Save new settings and exit Wizard
Commissioning
6.6 Application example
57