8.2.6.8
mA OUTPUT VALUE (2.6.8.)
Setting range:
Purpose:
Related parameters:
8.2.7
SIGNAL PROCESSING (2.7.)
8.2.7.1
NEAR RANGE (2.7.1.)
Factory setting:
Setting range:
Purpose:
Related parameters:
8.2.7.2
FAR RANGE (2.7.2.)
Note
Far Range can extend beyond the bottom of the vessel.
Factory setting:
Setting range:
Purpose:
Description:
Related parameters:
SITRANS LR560 (mA/HART)
Operating Instructions, 06/2017, A5E34647946-AD
Read only, 3.56 to 22.6 mA
Allows you to view the simulated value entered to test the functioning of the
loop.
MANUAL VALUE (2.6.7.) (Page 120)
0.278 m (0.91 ft)
0 to 45 m (0 to 131.2 ft) for 40 m device
0 to 105 m (0 to 344.5 ft) for 100 m device
The range in front of the device (measured from the sensor reference point)
within which any echoes will be ignored. This is sometimes referred to as
blanking or a dead zone.
UNITS (2.2.1.) (Page 111)
Value for Low Calibration Pt. + 5 m (16.4 ft)
Min. = Low Cal. Pt.
Max. = 40 m device: 45 m (131.2 ft), 100 m device: 105 m (344.5 ft)
Allows the material level to drop below Low Calibration Point without gen-
erating a Loss of Echo (LOE) state, see SENSOR MODE (2.2.2.)
(Page 111).
Use this feature if the measured surface can drop below the Low Cal. Point
in normal operation.
UNITS (2.2.1.) (Page 111)
CLEF RANGE (2.7.3.4) (Page 123)
Parameter Reference
8.2 SETUP (2.)
121