8.2.5.3
LEVEL (2.5.3.)
Note
MATERIAL LEVEL (2.5.1.) (Page 116) must be set to VALUE to enable the Level Value to
be reported.
Factory setting:
Setting range:
Purpose:
8.2.6
ANALOG OUTPUT SCALING (2.6.)
8.2.6.1
CURRENT OUTPUT FUNCTION (2.6.1.)
Note
• Level, space, and distance, have different reference points.
• Use caution when changing Current Output Function while the device is connected to a
HART network. Current Output Function controls the primary value and the loop current
for the device.
• Current Output Function also affects the secondary, tertiary and quaternary variables in a
HART network.
SITRANS LR560 (mA/HART)
Operating Instructions, 06/2017, A5E34647946-AD
3.56 mA
3.56 to 22.6 mA
Allows the user to define the mA value to be reported when the Fail-safe
timer expires.
Parameter Reference
8.2 SETUP (2.)
117