Operating
6.3 Remote operation
To set Service/Calibration schedules:
1. Open the menu Device – Maintenance, and click on the Service/Calibration Schedule tab.
2. Modify desired values and if desired, set reminders for either or both of Reminder 1 before
Lifetime (Required)/Reminder 2 before Lifetime (Demanded).
3. Click Write.
4. Click Read, to see the effects of your modification.
5. Click Service/Calibration Performed to reset the schedule.
6.3.6.11

Acknowledge faults

Open the menu Device – Acknowledge Faults, select the appropriate item from the
Extended Diagnostics pull-down menu, and click Transfer.
6.3.6.12

Wear

Reports the number of hours the device has been operating, and the number of times it has
been powered up.
Open the menu Device - Wear to view:
• Powered hours
• Power-on resets
6.3.6.13

Simulation

Note
The Simulation parameter influences output to the control system.
Two options enable you to test the functioning of the Analog Input Function Blocks or the
functioning of everything between the Transducer Block and Output. For more details see
Analog Input Function Blocks 1 and 2 (Page 197).
74
SITRANS LR200 with PROFIBUS PA
Operating Instructions, 07/2021, A5E32337680-AF