Mx2020 Ac Power Subsystem Electrical Specifications; Mx2020 Ac Power Supply Module Description; Table 55: Mx2020 Ac Power Subsystem Electrical Specifications - Juniper MX2020 Hardware Manual

3d universal edge router
Hide thumbs Also See for MX2020:
Table of Contents

Advertisement

MX2020 3D Universal Edge Router Hardware Guide

MX2020 AC Power Subsystem Electrical Specifications

Related
Documentation

MX2020 AC Power Supply Module Description

158
Connecting AC Power to an MX2020 Router with Three-Phase Wye AC Power
Distribution Modules on page 252
Replacing an MX2020 Three-Phase Delta AC Power Cord on page 504
Replacing an MX2020 Three-Phase Wye AC Power Cord
MX2020 Three-Phase Delta AC Power Distribution Module Specifications on page 163
MX2020 Three-Phase Wye AC Power Distribution Module Specifications on page 163
MX2020 AC Power Electrical Safety Guidelines on page 584
Table 55 on page 158
lists the AC power subsystem electrical specifications.

Table 55: MX2020 AC Power Subsystem Electrical Specifications

Item
AC input voltage
AC input line frequency
AC system current rating
AC system input power
Efficiency
MX2020 Three-Phase Delta AC Power Distribution Module Description on page 86
MX2020 Three-Phase Wye AC Power Distribution Module Description on page 88
MX2020 Three-Phase Delta AC Power Distribution Module Specifications on page 163
MX2020 Three-Phase Wye AC Power Distribution Module Specifications on page 163
MX2020 AC Power Electrical Safety Guidelines on page 584
The MX2020 supports a three-phase AC power system. There are two types of
three-phase power systems that can be installed in the router—three-phase delta or
Specification
Delta operating range: 200–240 VAC (line-to-line) (nominal)
Wye operating range: 200–240 VAC (line-to-neutral) (nominal)
Delta: 50/60 Hz (+/-3Hz)
Wye: 50/60 Hz (+/-3Hz)
Delta: 50 A @ 200 VAC–(input #1 for each PDM) and 25 A @ 200
VAC–(input #2 for each PDM)
Wye: 30 A @ 200 VAC–(input #1 for each PDM) and 15 A @ 200
VAC–(input #2 for each PDM)
Delta: 16800 W (input #1), 8400 W (input #2)
Wye: 16800 W (input #1), 8400 W (input #2)
90.5% at 50% load and 220 VAC IN
Copyright © 2015, Juniper Networks, Inc.

Advertisement

Table of Contents
loading

Table of Contents