Juniper MX104 Hardware Manual page 199

3d universal edge router
Hide thumbs Also See for MX104:
Table of Contents

Advertisement

Copyright © 2017, Juniper Networks, Inc.
b. The cable with very low resistance (indicating a closed circuit) to chassis ground
is the return cable (
+
For +24V:
a. The cable with very low resistance (indicating a closed circuit) to chassis ground
is the DC input cable (
b. The cable with very high resistance (indicating an open circuit) to chassis ground
is the return cable (
+
Secure each power cable lug to the terminal with the flat washers and screw (see
8.
Figure 57 on page
176). Apply up to 27.4 lb-in. (3.1 Nm) of torque to each screw. Do not
overtighten the screw. (Use a number 2 Phillips screwdriver.)
a. Secure the positive DC source power cable lug to the return (
b. Secure the negative DC source power cable lug to the input (
CAUTION:
Ensure that each power cable lug seats flush against the surface
of the terminal block as you are tightening the screws. Ensure that each
screw is properly threaded into the terminal. Applying installation torque
to the screw when improperly threaded may result in damage to the
terminal.
CAUTION:
The maximum torque rating of the terminal screws on the DC
power supply is 27.4 lb-in. (3.1 Nm). The terminal screws may be damaged
if excessive torque is applied. Use only a torque-controlled driver to tighten
screws on the DC power supply terminals. Use an appropriately sized
driver, with a maximum torque capacity of 27.4 lb-in. or less. Ensure that
the driver is undamaged and properly calibrated and that you have been
trained in its use. You may wish to use a driver that is designed to prevent
overtorque when the preset torque level is achieved.
Replace the clear plastic cover over the terminals on the faceplate.
9.
Connect each DC power cable to the appropriate external DC power source.
10.
NOTE:
For information about connecting to external DC power sources,
see the instructions for your site.
Switch on the external circuit breakers to provide voltage to the DC power source
11.
cable leads. Observe the system LED on the front of the router. If the DC power cable
is correctly installed and functioning normally, the system LED lights green steadily.
Chapter 23: Replacing Power System Components
).
).
).
+
) terminal.
) terminal.
175

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents