-4AD-PTW-ADP (4-channel Platinum Resistance Thermometer Data Input)
3U
3.2
Applicable Cable and Terminal Tightening Torque
Use the following cables to connect with the counterpart equipment. Terminate the cable end as shown below.
To connect the platinum resistance thermometer sensor, use the cable supplied with the Pt100 platinum
resistance thermometer or a twisted pair shielded cable.
1. Cables
Applicable cable and tightening torque
(stranded/single-wire)
Single-wire 0.3mm
(AWG22 to 20)
2-wire
0.3mm
Rod
0.3mm
terminal
(AWG22 to 20)
with
(Refer to the rod terminal
insulation
external view shown in
sleeve
the following figure.)
2. Termination of cable ends
To terminate the cable, treat the stranded/single wire directly or use a rod terminal with insulation sleeve.
• To directly terminate the end of a stranded/single-wire cable:
- Twist the end of the stranded cable so that the "barbed wires"
cannot protrude.
- Do not solder-plate the end of the cable.
• To terminate cable end using a rod terminal with insulation sleeve:
If the cable sheath is too thick, it may be difficult to insert the cable into
the insulation sleeve. For this reason, select an appropriate cable while
referring to the external view.
Manufacturer
Phoenix Contact
3. Tool
• To tighten terminals, use a small-sized screwdriver whose head is straight and is not widened as shown in
the figure to the right.
Note:
If the diameter of screwdriver grip is too small, tightening torque will not
be able to be achieved. Use the following recommended screwdriver or
an appropriate replacement (grip diameter: approximately 25mm).
Manufacturer
Phoenix Contact
I-12
Wire size
Tightening
torque
2
2
to 0.5mm
2
(AWG22)
0.22 N
2
2
to 0.5mm
0.25 N
Model
AI 0.5-8WH
3.2 Applicable Cable and Terminal Tightening Torque
• To connect a stranded cable, peel the cover off the cable
and then twist the core before connection.
• To connect a single-wire cable, just strip the cover off the
cable before connection.
m to
• Rod terminal with insulation sleeve
m
(recommended terminal)
AI 0.5-8WH : Manufactured by Phoenix Contact
• Caulking tool
CRIMPFOX ZA 3 : Manufactured by Phoenix Contact
(or CRIMPFOX UD 6 : Manufactured by Phoenix Contact)
Caulking tool
CRIMPFOX ZA 3
(or CRIMPFOX UD 6)
Type
SZS 0.4 × 2.5
Termination
Termination of cable end
9mm
(0.35")
Insulation sleeve
Contact area
(Crimp area)
8mm
2.6mm
14mm
(0.1")
(0.55")
The head
should be
straight.
0.4mm
2.5mm
(0.09")
(0.01")
3 Wiring