Selection Of The Thermocouple - Mitsubishi FX3U-4AD User Manual

Fx3g series fx3u series fx3uc series
Hide thumbs Also See for FX3U-4AD:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Analog Control Edition
3G
3U
3UC
FX
-4AD-TC-ADP (4-channel Thermocouple Data Input)
3U
3.4

Selection of the Thermocouple

3.4.1
Thermocouple type
• There are 2 types of thermocouples: K type and J type. When selecting the thermocouple type, make sure
that the same type of thermocouple is connection to all the channels.
• Be sure to use a non-grounded thermocouple type.
3.4.2
Compensating lead wire
To connect the thermocouple, use one of the following types of compensating lead wires:
Thermocouple
Type K
Type J
• The compensating lead wire indicates a temperature value of approximately 0.12
wire resistor (10Ω). Use the appropriate compensating lead wire when considering this difference.
• If the compensating lead wire is very long, the wire may be easily affected by noise, etc. It is, therefore,
recommended for the length of the compensating lead wire to be 100 m or less.
3.5
Wiring of Thermocouple
Wiring depends on the thermocouple type selected. Refer to the following wiring diagrams:
3.5.1
Wiring of thermocouple type K
*1.
It is not necessary to connect lines to the J-type terminals. Leave these terminals disconnected.
*2.
Keep the thermocouple away from inductive noise (commercial power, etc.).
K-14
KX,KCA,KCB,KCC
JX
Terminal block
OPEN*1
Thermocouple
Compensating
*2
type K
lead wire
Shield
24V DC
Class-D
grounding
L +, L -, ch :
represents the channel number.
Type of compensating lead wire
TC-ADP
Type J
Type J
Temperature
compensating circuit
3kΩ
ch
L +
L -
Temperature
compensating circuit
3kΩ
ch
L +
L -
+5V
24+
24-
3 Wiring
3.4 Selection of the Thermocouple
°
C higher than that of the