Fx3g series fx3u series fx3uc series
Hide thumbs Also See for FX3U-4AD:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Analog Control Edition
3G
3U
3UC
FX
-4AD/FX
-4AD (4-channel Analog Input)
3U
3UC
2. Caution regarding convenient function setting
• Even if the data addition function is used, the value before adding the addition data (BFM #61 to #64) will
be checked to detect the over-scale error.
• To use the peak value automatic transfer function (b4 of BFM #22), be sure to enable the peak value
holding function (b3 of BFM #22).
• To use the upper/lower limit error status data automatic transfer function (b5 of BFM #22), be sure to
enable the upper/lower limit value detection function (b1 of BFM #22).
• To use the abrupt change detection status data automatic transfer function (b6 of BFM #22), be sure to
enable the abrupt change detection function (b2 of BFM #22).
3. Caution regarding EEPROM writing
If data is written to BFM #0, #19, #21, #22, #125 to #129, or #198, the data will also be written to the 4AD
EEPROM.
→ For a detailed description of caution regarding EEPROM writing, refer to Subsection 5.4.1.