5.2.1
Buffer memory direct specification (FX
When directly specifying the buffer memory, specify the following device in the source or destination area of
the applied instruction as follows:
Unit number (0 to 7)
1. Example 1
If the following program is created, data in buffer memory (BFM #10) of unit 1 will be multiplied by the data
(K10), and then the multiplication result will be output to the data registers (D10, D11).
READ command
Unit number
Buffer memory number
2. Example 2
If the following program is created, the value in the data register (D20) is added to K10 and written to buffer
memory (BFM #6) of unit 1.
WRITE command
Augend
5.2.2
FROM/TO instruction (FX
1. FROM instruction (Reading out BFM data to PLC)
Use FROM instruction to read out the data from the buffer memory.
In a sequence program, use this instruction as follows:
READ command
Unit number
Buffer memory number
If the above program is created, 1 point of data will be read out from the buffer memory BFM #10 of unit No.1
to the data register (D10).
2. TO instruction (Writing PLC data into BFM)
Use the TO instruction to write data to a buffer memory.
In a sequence program, use this instruction as follows:
WRITE command
Unit number
Buffer memory number
If the above program is created, 1 point of data (H3300) will be written to buffer memory (BFM #0) of unit
No.1.
U \G
FNC 22
U1\G10
MUL
FNC 20
D20
ADD
, FX
, FX
3G
3U
FNC 78
K1
K10
FROM
FNC 79
K1
K0
TO
, FX
PLC only)
3U
3UC
Enter a numeric value in
Buffer memory number (0 - 3098)
K10
D10
Multiplication result
Multiplier
K10
U1\G6
(
Unit number
Addition
Buffer memory number
result
Addend
PLC)
3UC
D10
K1
Number of transfer
data points
Transfer-to register
H3300
K1
Number of transfer
data points
Transfer source
5 Buffer Memory (BFM)