Mitsubishi FX3U-4AD User Manual page 284

Fx3g series fx3u series fx3uc series
Hide thumbs Also See for FX3U-4AD:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Analog Control Edition
3G
3U
3UC
FX
-4DA-ADP (4-channel analog Output)
3U
4.5
Output Setting Data
The 4DA-ADP performs D/A conversion on the output setting data (digital data) into analog data, and outputs
the analog data.
Use the special data registers shown in the following table for the output setting data:
• FX
, FX
3U
3UC
Special data register
1st
D8260
D8270
D8261
D8271
D8262
D8272
D8263
D8273
• FX
Series PLC
3G
Special data register
1st
D8280
D8290
D8281
D8291
D8282
D8292
D8283
D8293
1. Program Example (For FX
M8000
Normally ON
Using the indicator or the sequence program, input the digital data to be subject to D/A conversion (to be
output as analog data) in D100 and D101.
F-20
Series PLC
2nd
3rd
4th
D8280
D8290
D8281
D8291
D8282
D8292
D8283
D8293
2nd
Channel-1 output setting data
Channel-2 output setting data
Channel-3 output setting data
Channel-4 output setting data
, FX
3U
3UC
FNC 12
D100
MOV
FNC 12
D101
MOV
Channel-1 output setting data
Channel-2 output setting data
Channel-3 output setting data
Channel-4 output setting data
Description
Series PLC)
Performs D/A conversion using the digital
D8260
data stored in the D100 for channel 1 of
the 1st analog special adapter.
Performs D/A conversion using the digital
data stored in the D101 for channel 2 of
D8261
the 1st analog special adapter.
4 Programming
4.5 Output Setting Data
Numeric data type: Decimal (K)
Description

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents