PLC User's Manual - Analog Control Edition
3G
3U
3UC
FX
-4DA (4-channel Analog Output)
3U
6
Create a sequence program.
To change the output characteristics, write the offset data (BFM #10 to #13) and the gain data
(BFM #14 to #17) in the sequence program, and then turn on the corresponding bit of BFM #9 for
the corresponding channel.
Example: Program for changing the output characteristics of channels 1 and 2 (For FX
Series PLCs):
X000
M0
T0
7
Transfer the sequence program to change the output characteristics.
Transfer the sequence program, and start the PLC.
After the PLC is started and the output characteristic write command (X000) is turned on, the offset
data and gain data will be written.
Since the offset data and gain data are stored in the EEPROM incorporated in FX
sible to delete the pre-written sequence program.
8
Check the analog output signals
Check that the output analog signals correspond to the set output data.
FNC 12
K3030
MOV
P
FNC 12
HFF00
MOV
P
SET
K50
T0
FNC 16
K1000
U0\G10
FMOV
P
FNC 16
K3000
U0\G14
FMOV
P
FNC 12
H0003
MOV
P
FNC 12
K0
MOV
P
→ If analog signals are not correctly output, refer to Chapter 9 "Troubleshooting."
Cancellation of setting change
U0\G19
prohibition mode
Output mode specification for
U0\G0
channels 1 to 4
M0
Setting of offset data (channels 1 and 2)
K2
K2
Setting of gain data (channels 1 and 2)
Offset/gain setting value write command
U0\G9
Setting change prohibition
U0\G19
7 Changing Output Characteristic
7.1 Procedure for Changing Output Characteristics
3U
-4DA, it is pos-
3U
A
B
, FX
3UC
C
D
E
F
G
H
I
J
E-55