Mitsubishi FX3U-4AD User Manual page 63

Fx3g series fx3u series fx3uc series
Hide thumbs Also See for FX3U-4AD:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Analog Control Edition
3G
3U
3UC
Common Items
4.4.4
FX
-4AD-TC-ADP
3U
Specifications
Number of input points
Input signal
• Type K: -100°C to +1000°C
Rated temperature range
• Type J: -100°C to +600°C
• Type K: -1000 to +10000
Digital output
• Type J: -1000 to +6000
• Type K: 0.4°C
Resolution
• Type J: 0.3°C
Overall accuracy
Time required for
• FX
conversion
• FX
• Type K
Input characteristics
• Type J
• The photocoupler is used to insulate the analog input area from the PLC.
Insulation method
• The DC/DC converter is used to insulate the power supply from the analog inputs.
• Channels are not insulated from each other.
Number of I/O points
0 points
occupied
(This number of points is not related to the maximum number of input/output points of the PLC.)
Centigrade(°C)
/FX
Series PLC : 200µs (Data updated every scan time.)
3U
3UC
Series PLC : 250µs (Data updated every scan time.)
3G
+10100
+10000
-110°C
0
+1000°C
Temperature
-1000
-1100
+6100
+6000
-100°C
0
+600°C
Temperature
-1000
-1100
4 Comparison of Performance Specifications
FX
-4AD-TC-ADP
3U
4ch
Thermocouple type K or J
JIS C 1602-1995
• Type K: -148°F to +1832°F
• Type J: -148°F to +1112°F
• Type K: -1480 to +18320
• Type J: -1480 to +11120
• Type K: 0.72°F
• Type J: 0.54°F
±(0.5% for full scale +1°C)
• Type K
+18500
+18320
-148°F
-1660
• Type J
+11300
+11120
-148°F
-1660
4.4 Temperature Sensor Input
Fahrenheit(°F)
0
+1832°F
Temperature
-1480
0
+1112°F
Temperature
-1480
A-41
A
B
C
D
E
F
G
H
I
J