Averaging Time - Mitsubishi FX3U-4AD User Manual

Fx3g series fx3u series fx3uc series
Hide thumbs Also See for FX3U-4AD:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Analog Control Edition
3G
3U
3UC
FX
-4AD-PNK-ADP (4-channel Resistance Thermometer Data Input)
3U
4.6

Averaging Time

If the averaging time is set for the PNK-ADP, the averaged temperature measurement data will be stored in
the D8260 to D8263, D8270 to D8273, D8280 to D8283, and D8290 to D8293. The averaging time can be set
for each channel.
Set the averaging time in the following special data registers:
• FX
, FX
3U
3UC
1st
D8264
D8265
D8266
D8267
• FX
Series PLC
3G
Special data register
1st
D8284
D8285
D8286
D8287
1. Cautions regarding averaging time setting
• If the averaging time is set to "1", the immediate data will be stored in the temperature measurement
special data register.
• If the averaging time is set to "2" or more, the average value will be calculated in accordance with the set
averaging time, and the average value obtained will be stored in the temperature measurement special
data register.
• After turning the PLC power on, the average data will be stored in the temperature measurement special
data registers (D8260 to D8263, D8270 to D8273, D8280 to D8283, and D8290 to D8293) until the number
of data items is increased to the set averaging time.
• Set the averaging time in the range from 1 to 4095. If the set value is outside the setting range, the error
signal will be output.
2. Program Example (For FX
M8000
Normally
ON
J-22
Series PLC
Special data register
2nd
3rd
D8274
D8284
D8275
D8285
D8276
D8286
D8277
D8287
2nd
D8294
Averaging time for channel-1 data
D8295
Averaging time for channel-2 data
D8296
Averaging time for channel-3 data
D8297
Averaging time for channel-4 data
→ For a detailed description of error status, refer to Section 5.5
, FX
3U
3UC
FNC 12
MOV
FNC 12
MOV
4th
D8294
Averaging time for channel-1 data
D8295
Averaging time for channel-2 data
D8296
Averaging time for channel-3 data
D8297
Averaging time for channel-4 data
Description
Series PLC)
Sets the averaging time to "32" for the channel-1
K32
D8264
data of the 1st analog special adapter.
Sets the averaging time to "128" for the channel-2
K128
D8265
data of the 1st analog special adapter.
4 Programming
4.6 Averaging Time
Setting range: 1 to 4095
Initial value: K64
Numeric data type: Decimal (K)
Description