Input Data

The data converted by the 4AD-ADP will be stored in the special data registers.
The special data registers that store the input data are shown in the following table:
• FX
, FX
Series PLC
3U
3UC
1st
D8260
D8261
D8262
D8263
• FX
Series PLC
3G
Special data register
1st
D8280
D8281
D8282
D8283
The converted A/D immediate data or averaged data (data average conforming to the specified averaging
time) will be stored in the above data registers as the input data.
1. Caution regarding input data
Input data is for reading only.
Do not change (rewrite) the input data using sequence program, indicator, or device monitor of the
programming tool.
2. Program Example (For FX
M8000
Normally
ON
Even if the input data is not stored in D100 or D101, data registers D8260 or D8261 can be directly used in
the timer/counter set value or in a PID instruction.
Special data register
2nd
3rd
D8270
D8280
D8271
D8281
D8272
D8282
D8273
D8283
2nd
D8290
Stores the channel-1 input data
D8291
Stores the channel-2 input data
D8292
Stores the channel-3 input data
D8293
Stores the channel-4 input data
→ For a detailed description of the averaging time, refer to Section 4.5.
, FX
Series PLC)
3U
3UC
FNC 12
D8260
MOV
FNC 12
D8261
MOV
4th
D8290
Stores the channel-1 input data
D8291
Stores the channel-2 input data
D8292
Stores the channel-3 input data
D8293
Stores the channel-4 input data
Description
Stores the channel-1 input data
D100
of the 1st analog special
adapter in the D100.
Stores the channel-2 input data
D101
of the 1st analog special
adapter in the D101.