Buffer Memory Reading/Writing Method - Mitsubishi FX3U-4AD User Manual

Fx3g series fx3u series fx3uc series
Hide thumbs Also See for FX3U-4AD:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Analog Control Edition
3G
3U
3UC
FX
-4AD/FX
-4AD (4-channel Analog Input)
3U
3UC
5.2

Buffer Memory Reading/Writing Method

To read or write to the 4AD buffer memory, use the FROM/TO instructions or buffer memory direct
*1
specifications
.
However, to use buffer memory direct specification
required.
*1.
This function is supported only in FX
5.2.1
Buffer memory direct specification (FX
When directly specifying the buffer memory, specify the following device in the source or destination area of
the applied instruction as follows:
Unit number (0 to 7)
1. Example 1
If the following program is created, data in buffer memory (BFM #10) of unit 1 will be multiplied by the data
(K10), and then the multiplication result will be output to data registers (D10, D11).
READ command
Unit number
Buffer memory number
2. Example 2
If the following program is created, the value in data register (D20) is added to K10 and written to buffer
memory (BFM #6) of unit 1.
WRITE command
Augend
5.2.2
FROM/TO instruction (FX
1. FROM instruction (Reading out BFM data to PLC)
Use the FROM instruction to read the data from the buffer memory.
In a sequence program, use this instruction as follows:
READ command
Unit number
Buffer memory number
If the above program is created, 1 point of data will be read out from the buffer memory BFM #10 of unit No.1
to data register D10.
2. TO instruction (Writing PLC data into BFM)
Use the TO instruction to write data to a buffer memory.
In a sequence program, use this instruction as follows:
WRITE command
Unit number
Buffer memory number
If the above program is created, 1 point of data (H3300) will be written to buffer memory BFM #0 of unit No.1.
3U
→ For a detailed description of software compatible with the FX
U \G
FNC 22
U1\G10
MUL
FNC 20
D20
ADD
, FX
, FX
3G
3U
FNC 78
K1
K10
FROM
FNC 79
K1
K0
TO
*1
, software compatible with FX
/FX
PLCs.
3UC
, FX
PLC only)
3U
3UC
Enter a numeric value in
Buffer memory number (0 - 6999)
K10
D10
Multiplication result
Multiplier
K10
U1\G6
Addition
result
Addend
PLC)
3UC
D10
K1
Number of transfer
data points
Destination register
H3300
K1
Number of transfer
data points
Transfer source
5 Buffer Memory (BFM)
5.2 Buffer Memory Reading/Writing Method
/FX
Series PLCs is
3U
3UC
/FX
Series PLC,
3U
3UC
refer to Section 1.4.
(
)