Mitsubishi FX3U-4AD User Manual page 289

Fx3g series fx3u series fx3uc series
Hide thumbs Also See for FX3U-4AD:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Analog Control Edition
3G
3U
3UC
FX
-4DA-ADP (4-channel analog Output)
3U
3. Example of program 2 (For FX
• For example, create the following program to change the digital output data (D100) of the 1st analog
special adapter.
M8001
FNC 230
D100
LD>=
M10
4. Cautions regarding programming
• GX Developer version 8.13P or later supports scaling instruction (SCL/FNC259).
• If the input digital value for the D/A conversion is out of the data table range specified by scaling instruction
(SCL/FNC259), the FX Series PLC will detect an operation error (error code: K6706).
Series PLC)
3G
FNC 237
K0
D100
K10000
AND<=
FNC 22
D100
MUL
FNC 23
D101
K10000 D103
DDIV
FNC 20
D103
ADD
FNC 12
MOV
5 Changing of Output Characteristics
5.1 Example: Changing of Voltage Output Characteristics
Sets the output mode of channel 1 to the
M8280
voltage output mode.
Sets the output holding function for
M8284
channel 1.
Check to make sure the digital
M10
value (D100) is in range.
K1600
D101
Calculation for changing output
characteristics.
Stores the operation result in D8280.
K400
D107
D107
D8280
A
B
C
D
E
F
G
H
I
J
F-25