Fx 3U -4Da - Mitsubishi FX3U-4AD User Manual

Fx3g series fx3u series fx3uc series
Hide thumbs Also See for FX3U-4AD:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Analog Control Edition
3G
3U
3UC
Common Items
4.2.3
FX
-4DA
3U
Specifications
Number of output points
Analog output range
Offset
Gain
Digital input
Resolution
Ambient temperature:
25±5°C
Ambient temperature:
0 to 55°C
Reference
Time required for D/A
conversion
Output characteristics
Insulation method
Number of I/O points
occupied
*1.
Adjustment of the offset or gain value will not affect the resolution. In the analog value specification
mode, however, the offset/gain cannot be adjusted.
*2.
The offset and the gain should satisfy the following condition:
≤ (Gain - Offset) ≤ 10V
1V
*3.
The offset and the gain should satisfy the following condition:
≤ (Gain - Offset) ≤ 30mA
3mA
*4.
Adjustment of the offset or gain value will not affect the resolution.
Voltage output
-10V to +10V DC
(External load: 1k to 1MΩ)
*1,*2
-10V to +9V
*1,*2
-9V to +10V
With sign, 16 bits, binary
0.32mV(20V×1/64000)
±0.3%(±60mV) for 20V full scale
±0.5%(±100mV) for 20V full scale
Includes corrective function by load fluctuation.
1ms (The number of selected channels will not affect this value.)
When the output mode is set to "0":
+10.2V
+10V
-32000
0
+32000
-10V
-10.2V
• The photocoupler is used to insulate the analog output area from the PLC.
• The DC/DC converter is used to insulate the power supply from the analog output.
• Channels are not insulated from each other.
8 points (Taken from either the input or output points of the PLC.)
4 Comparison of Performance Specifications
FX
-4DA
3U
4ch
(External load: 500Ω or less)
*4
0.63µA(20mA×1/32000)
±0.3%(±60µA) for 20mA full scale
Same accuracy for 4mA to 20mA output
±0.5%(±100µA) for 20mA full scale
Same accuracy for 4mA to 20mA output
When the output mode is "2":
(The dotted line is for mode 3.)
20.4mA
20mA
4mA
4.2 Analog Output
Current output
0mA to 20mA DC
4mA to 20mA DC
*1,*3
0mA to 17mA
*1,*3
3mA to 30mA
15 bits, binary
*4
-
0
32000
Digital input