PLC User's Manual - Analog Control Edition
3G
3U
3UC
FX
-4AD/FX
-4AD (4-channel Analog Input)
3U
3UC
BFM number
Channel-1 upper limit value error setting
#81
(Valid if b1 of BFM #22 is set to ON)
Channel-2 upper limit value error setting
#82
(Valid if b1 of BFM #22 is set to ON)
Channel-3 upper limit value error setting
#83
(Valid if b1 of BFM #22 is set to ON)
Channel-4 upper limit value error setting
#84
(Valid if b1 of BFM #22 is set to ON)
#85 to #90
Not used
Channel-1 abrupt change detection value
#91
(Valid if b2 of BFM #22 is set to ON)
Channel-2 abrupt change detection value
#92
(Valid if b2 of BFM #22 is set to ON)
Channel-3 abrupt change detection value
#93
(Valid if b2 of BFM #22 is set to ON)
Channel-4 abrupt change detection value
#94
(Valid if b2 of BFM #22 is set to ON)
#95 to #98
Not used
Clear of upper/lower limit error data or abrupt
#99
change error data
#100
Not used
Channel-1 minimum peak value (Valid if b3 of
#101
BFM #22 is set to ON)
Channel-2 minimum peak value (Valid if b3 of
#102
BFM #22 is set to ON)
Channel-3 minimum peak value (Valid if b3 of
#103
BFM #22 is set to ON)
Channel-4 minimum peak value (Valid if b3 of
#104
BFM #22 is set to ON)
#105 to #108
Not used
#109
Minimum peak value resetting
#110
Not used
Channel-1 maximum peak value (Valid if b3
#111
of BFM #22 is set to ON)
Channel-2 maximum peak value (Valid if b3
#112
of BFM #22 is set to ON)
Channel-3 maximum peak value (Valid if b3
#113
of BFM #22 is set to ON)
Channel-4 maximum peak value (Valid if b3
#114
of BFM #22 is set to ON)
#115 to #118
Not used
#119
Maximum peak value resetting
#120 to #124
Not used
Peak values (Minimum: BFM #101 to #104 /
Maximum: #111 to #114) automatic transfer-
*2
to first data register specification (Valid if b4 of
#125
BFM #22 is set to ON / Occupies of 8
consecutive points)
*1.
Use b0 to b2.
*2.
If power failure occurs, the EEPROM will retain its data.
*3.
Use b0 to b3.
B-26
Description
Setting range
Initial value
Maximum digital
value in input range
From lower limit
Maximum digital
value error setting
value in input range
value to maximum
Maximum digital
digital value in
value in input range
input range
Maximum digital
value in input range
-
From 1 to 50% of
5% of full scale
full scale
From 1 to 50% of
5% of full scale
full scale
From 1 to 50% of
5% of full scale
full scale
From 1 to 50% of
5% of full scale
full scale
-
*1
H0000
-
-
-
-
-
-
*3
H0000
-
-
-
-
-
-
*3
H0000
-
0 to 7992
K200 at delivery
5 Buffer Memory (BFM)
5.3 Buffer Memory List (BFM)
Data type
Reference
Decimal
Decimal
Subsection
5.4.16
Decimal
Decimal
-
-
Decimal
Decimal
Subsection
5.4.17
Decimal
Decimal
-
-
Subsection
-
5.4.18
-
-
-
Decimal
-
Decimal
Subsection
5.4.19
-
Decimal
-
Decimal
-
-
Hexadeci-
Subsection
mal
5.4.20
-
-
-
Decimal
-
Decimal
Subsection
5.4.19
-
Decimal
-
Decimal
-
-
Hexadeci-
Subsection
mal
5.4.20
-
-
Subsection
Decimal
5.4.21
-
-
-
-
-
-
-