D/A Conversion Time
This section describes the D/A conversion time.
2.4.1
When connected to a FX
1. D/A conversion and special data register update timing
D/A conversion is performed at every scan time of the PLC.
During execution of the END instruction, the PLC writes the output setting data of the special data registers,
performs D/A conversion of the data, and updates the analog output data.
FX
-4DA-ADP
3U
n'th
D/A
conversion
200µs/4ch
2. D/A conversion during PLC stop
If the output holding function cancellation setting is disabled by the special device, the offset value will be
output.
If the output holding function cancellation setting is enabled, the output at switching from RUN to STOP will be
latched.
Just after power-on, however, the offset value will be output until operation begins.
3. If two or more analog special adapters are connected
During execution of the END instruction, data in all the connected adapters will be subject to D/A conversion
and then output (in the order of 1st adapter → 2nd adapter... 4th adapter).
4. D/A conversion speed (data update time)
During execution of END instruction, the output setting digital data per of 4 channel will be subject to D/A
conversion which takes 200µs, after which the analog data will be output.
END instruction execution time will be "200µs × number of connected adapters."
F-8
, FX
PLC
3U
3UC
FX
-4DA-ADP
3U
1st
Digital value
D/A
writing
conversion
D/A conversion
200µs
start command
/4ch
Digital value writing
D/A conversion
start command
2.4 D/A Conversion Time
FX
/FX
Series PLC
3U
3UC
Sequence
program
END instruction
2 Specifications