3. Current input characteristics [-20 to +20mA] (Input mode: 6 to 8)
Set input mode: 6
Input type: Current input
Analog input range: -20 to +20mA
Digital output range: -16000 to +16000
Offset/gain adjustment: Possible
Digital value
+16320
+16000
Current
-20mA
Input
B-10
Set input mode: 7
Input type: Current input
Analog input range: -20 to +20mA
Digital output range: -4000 to +4000
Offset/gain adjustment: Possible
Current
0
Input
+20mA
-16000
-16320
Digital value
+4080
+4000
-20mA
0
+20mA
-4000
-4080
2 Specifications
2.4 Input Mode (Characteristics) BFM #0
Set input mode: 8
Input type: Current input
(analog value direct indication)
Analog input range: -20 to +20mA
Digital output range: -20000 to +20000
Offset/gain adjustment: Impossible
Digital value
+20400
+20000
Current
-20mA
0
Input
+20mA
-20000
-20400