Mitsubishi FX3U-4AD User Manual page 252

Fx3g series fx3u series fx3uc series
Hide thumbs Also See for FX3U-4AD:
Table of Contents

Advertisement

FX
/FX
/FX
PLC User's Manual - Analog Control Edition
3G
3U
3UC
FX
-4DA (4-channel Analog Output)
3U
3
Determine the output characteristics to be changed.
Example: Change to output voltage of 1 to 5 V with digital values 0 to 32000
Output mode: 0
Output characteristics provided at the time
of factory shipment
Voltage output value
+10.2V
+10V
-32000
4
Determine the offset data.
Determine the analog output value for the digital output value of 0.
Set the analog output value in mV for the voltage output mode, and the analog output value in µA
for the current output mode.
Example: To set the offset value of 1 V, set 1000 mV.
5
Determine the gain data.
Determine the analog output value for the digital output value of 16000.
Set the analog output value in mV for the voltage output mode, and the analog output value in µA
for the current output mode.
Example: To set the gain value of 3 V, set 3000 mV.
(5-1)÷2+1 = 3V (3000 mV)
E-54
Digital
0
value
+32000
-10V
-10.2V
→ For a detailed description of the offset data, refer to Subsection 5.4.6.
→ For a detailed description of the gain data, refer to Subsection 5.4.6.
7 Changing Output Characteristic
7.1 Procedure for Changing Output Characteristics
Output characteristics newly provided
Voltage output value
5V
1V
0
Digital
value
32000

Hide quick links: