Wiring The Et 200S - Siemens Simatic ET 200S Operating Instructions Manual

Distributed i/o system
Hide thumbs Also See for Simatic ET 200S:
Table of Contents

Advertisement

5.4

Wiring the ET 200S

5.4
5.4.1
Wiring rules for the ET 200S
Wiring rules
Wiring rules for ...
Connectable wire cross-sections for
solid wires
permitted cross-
Without end sleeve
sections of
With end sleeve
flexible
conductors
Number of wires per connection
Maximum external diameter of the wire
insulation
Stripped wire length
End sleeves in
Without insulating
accordance with
collar
DIN 46228
with insulating collar
0.25 to 1.5 mm
ET 200S
Operating Instructions, 12/2005, A5E00515771-03
Interface module (supply
voltage)
No
0.25 mm to 2.5 mm
0.25 mm to 1.5 mm
1 or a combination of 2 conductors up to 1.5 mm
(total) in a common end sleeve
O̸ 3.8 mm
11 mm
Form A, 8 to 12 mm long
Form E, up to 12 mm long
2
Terminal modules (spring
and screw terminals)
0.14 mm to 2.5 mm
0.14 mm to 2.5 mm
2
0.14 mm to 1.5 mm
2
O̸ 3.1 mm at 1.5 mm
O̸ 3.8 mm at 2.5 mm
Form A, up to 12 mm long
Wiring and assembly
5.4 Wiring the ET 200S
Terminal modules (Fast
Connect)
0.5 mm to 1.5 mm
2
0.5 mm to 1.5 mm
2
---
2
1
2
O̸ 3.2 mm at 1.5 mm
2
2
---
---
---
2
2
2
5-7