Analog input module error types
The table below shows the error types on power modules
Table 8-12
Analog input module error types
Analog input modules
2AI U
2AI U ST
HS
2AI U HF
2AI I 2WIRE ST
4AI I 2WIRE ST
2AI I 2WIRE HS
2AI I 4WIRE ST
2AI I 2/4WIRE HF
2AI I 4WIRE HS
2AI RTD ST
2AI RTD HF
---
---
---
In the case of the 2AI RTD High Feature, a wire break is reported for the measuring and constant-current lines of the
1
sensor.
The following applies for the modules 2AI TC ST and 2AI TC HF:
2
Reference channel error is not reported if the RTD module is not parameterized in the GSD file with the PT100 climate.
This applies to IM151-1 HIGH FEATURE (6ES7151-1BA00-0AB0 or higher), IM151-7 CPU and IM151-3 PROFINET IO
6ES7151-3AA00-0AB0 or higher).
ET 200S
Operating Instructions, 12/2005, A5E00515771-03
Error class
2AI TC ST
16
10000: Parameter
D
assignment error
2AI TC HF
9
01001: Fault
D
7
00111: Violation of
D
higher limit
8
01000: Lower value
D
limit fallen below
6
00110:
D
Wire break
21
10101:
D
Reference channel
error
2
8.1 Alarm, error and system messages on PROFIBUS DP
Meaning
Module cannot use the
parameter for the
channel:
Inserted module does
not match the one
configured.
Faulty parameter
assignment.
Internal module error
(diagnostics message
at channel 0 applies to
the entire module)
Value is above the
overrange.
Value is below the
underrange. Short-
circuit at module 2AI
RDT HF with
configuration of the
PTC channel.
Line to the sensor
interrupted.
1
Error on the reference
channel
Alarm, error and system messages
Remedy
Correct the configuration
(align actual and preset
configuration).
Correct the parameter
assignment (diagnostics
wire break only for the
allowed measuring
range parameterized).
Replace the module.
Correct the
module/actuator tuning.
Correct the
module/actuator tuning.
Correct the process
wiring.
Check the reference
module (2AI RTD
Standard).