3.3 Limitation of connectable modules/maximum configuration
• Address space:
• Power modules / COMPACT modules: Maximum configuration per voltage group
Table 3-6
Power module PM-E
24 VDC
Power module PM-E
24 ..48 VDC
Power module PM-E
24 ..48 VDC/24 ..230 VAC
IM151-1 COMPACT
This value applies to I/O modules connected after IM151-1 COMPACT.
1
• Number of identifiers: Per module one identifier (max. 63 identifiers)
• You can use the ET 200S with DP masters with a diagnostic frame length of 32 bytes
3-12
on the PROFIBUS DP (depends on the DP master)
– IM151-1 BASIC interface module supports a maximum of 88 input bytes or 88 output
bytes.
– Interface module IM151-1 COMPACT supports maximum 100 input bytes or 100
output bytes.
– interface modules IM151-1 STANDARD and IM151-1 FO STANDARD supported
Maximum 128 input bytes or 128 output bytes
(up to 6ES7151-1AA03-0AB0 or 6ES7151-1AB02-0AB0)
Maximum 244 input bytes or 244 output bytes
(from 6ES7151-1AA04-0AB0)
– The IM151-1 HIGH FEATURE interface module supports a maximum of 244 input
bytes or 244 output bytes.
on PROFINET IO
– The IM151-3 PN or IM151-3 PN HIGH FEATURE interface module supports a
maximum of 256 input bytes or 256 output bytes.
Maximum configuration per voltage group
Power modules /
COMPACT modules:
32DI
16DI/16DO
because you can set the length of the diagnostic frame in all the interface modules.
Maximum current-
carrying capacity
10 A
10 A
10 A (24 VDC)
8 A (120 /230 VAC)
5 A
1
Connectable modules
The number of modules that can be
connected depends on the total current of all
the modules in this voltage group. This must
not exceed the maximum current-carrying
capacity in total. The total current is governed
in large part by the digital output modules:
2DO 24 VDC/0.5 A ST
2DO 24 VDC/0.5 A HF
4DO 24 VDC/0.5A ST
4DO 24 VDC/0.5A HF
2DO 24 VDC/2A ST
2DO 24 VDC/2 A HF
4DO 24 VDC/2A ST
4DO 24 VDC/2A HF
2DO 24 ...230 VAC/2A